Voltage Drop Calculator (AWG & mm²)

Voltage drop, load voltage and power lost in a copper or aluminium cable, DC, single- or three-phase, plus the smallest AWG or mm² size within your limit.

Length is source to load; the return conductor is added automatically.

The drop is 2.65 %, within your 3 % limit.

Voltage drop
Drop (% of supply)
Voltage at the load
Power lost in the cable
Resistance per conductor
Cross-section
Smallest AWG within the limit
Smallest metric size within the limit

DC resistance of solid conductors; AC reactance and stranding are not included. Check ampacity separately.

How to use

  1. Pick the system (DC, single-phase or three-phase) and the conductor material, then the size as an AWG gauge or in mm².
  2. Enter the one-way length, the current, the supply voltage, the conductor temperature and the largest drop you will accept.
  3. Read the drop, the load voltage and the loss, and the smallest AWG and metric sizes that meet your limit.

About this tool

Show

Works out how much voltage a cable loses on the way to the load. Choose DC, single-phase or balanced three-phase, copper or aluminium, and give the conductor size as an AWG gauge or a cross-section in mm², the one-way run length, the current, the supply voltage and the conductor temperature. The tool returns the drop in volts and as a percentage of the supply, the voltage left at the load, the power turned into heat in the cable, the resistance per kilometre and per 1,000 ft, and the smallest AWG gauge and the smallest standard metric size that would keep the drop within the limit you set. Resistance comes from first principles: copper at the IACS value of 1/58 Ω·mm²/m at 20 °C, aluminium at 61 % of that, corrected linearly for temperature, and AWG diameters from ASTM B258 — which reproduces the NEC Chapter 9 Table 8 resistances for solid conductors at 75 °C. The drop is 2·I·R for DC and single-phase (out and back) and √3·I·R per phase for a balanced three-phase load. What it leaves out: the reactance of AC cables, which matters from roughly 25 mm² (4 AWG) upward and adds a few percent at low power factor; the small extra resistance of stranded conductors; and skin effect at high frequency. Codes and standards set the limits — 3 % for a branch circuit and 5 % overall is a common recommendation in the NEC, and IEC 60364 uses 3 % for lighting and 5 % for other loads — and they also require a size that carries the current without overheating, which this tool does not check; use an ampacity table for that.

Frequently asked questions

Is the length one way or round trip?

One way — the distance from the source to the load. The tool doubles it for the return conductor in DC and single-phase circuits and uses √3 for three-phase.

Why does temperature change the result?

Copper's resistance rises about 0.39 % per °C. A cable running at 75 °C, the rating often used for sizing, has about 22 % more resistance than at 20 °C.

How much voltage drop is acceptable?

It depends on the code and the load. The NEC recommends no more than 3 % on a branch circuit and 5 % in total; IEC 60364 suggests 3 % for lighting and 5 % for other uses. Low-voltage DC systems such as 12 V solar often aim for 2–3 %.

Does a larger wire always fix the drop?

Yes, drop falls in proportion to cross-section, but the size must also meet ampacity for the current and installation method, which is a separate check this tool does not make.

Why does the result differ slightly from a table?

Tables often list stranded conductors, coated copper or include AC reactance. This tool uses the solid-conductor DC resistance, which matches NEC Table 8 for solid copper.