Psychrometric Calculator (Moist Air Properties)

From dry bulb plus relative humidity, wet bulb, dew point or humidity ratio, get every moist-air property: enthalpy, specific volume, density and more.

Relative humidity
Wet-bulb temperature
Dew point
Humidity ratio
Enthalpy (per kg dry air)
Specific volume (per kg dry air)
Moist-air density
Absolute humidity
Vapour pressure
Saturation pressure
Degree of saturation
Pressure used

ASHRAE Handbook — Fundamentals 2017, chapter 1, computed in your browser.

How to use

  1. Enter the dry-bulb temperature in °C or °F.
  2. Choose which humidity value you know and enter it, then give the pressure in kPa or the altitude in metres.
  3. Read the full set of properties and click any one to copy it.

About this tool

Show

Computes the state of moist air the way HVAC engineers do, with the equations of the ASHRAE Handbook — Fundamentals (2017), chapter 1. Give the dry-bulb temperature and any one humidity measure — relative humidity, thermodynamic wet-bulb temperature, dew point or humidity ratio — plus the barometric pressure, or an altitude from which the standard pressure is derived, and it returns all the others: relative humidity, wet bulb, dew point, humidity ratio in g/kg and grains per pound, specific enthalpy, specific volume, moist-air density, absolute humidity, vapour and saturation pressures and the degree of saturation. Saturation pressure uses the Hyland–Wexler formulas, over ice below the triple point and over water above it, so frost points and wet bulbs below freezing come out right; the wet bulb and dew point are solved to far below a thousandth of a degree. The results match PsychroLib, an independent implementation of the same handbook equations, and reproduce the handbook's own worked example (40 °C dry bulb, 20 °C wet bulb gives 14 % RH and 56.7 kJ/kg). Limits worth knowing: the equations treat air and vapour as ideal gases, which is accurate to a fraction of a percent at ordinary pressures but not in compressed-air systems; the wet bulb is the thermodynamic one, which a real sling psychrometer only approaches when the airflow is fast enough; and a state wetter than saturation (fog) is refused rather than computed.

Frequently asked questions

What is the difference between wet bulb and dew point?

The dew point is the temperature at which the air's water vapour starts to condense if it is cooled without changing its moisture. The wet bulb is the temperature a wetted surface reaches by evaporative cooling; it lies between the dew point and the dry bulb.

Why does pressure matter?

The same relative humidity at altitude holds more water per kilogram of air, because the dry air is thinner. At 1,600 m the humidity ratio for 50 % RH at 25 °C is about a fifth higher than at sea level.

What is enthalpy used for?

It is the heat content of moist air per kilogram of dry air. The difference in enthalpy across a cooling coil, multiplied by the air mass flow, gives the coil's total load, sensible plus latent.

Why is my state refused as supersaturated?

A humidity ratio above the saturation value at that temperature means liquid water or fog is present, which the moist-air equations do not describe.

Why does a dew point below 0 °C say ice?

Below the triple point the vapour condenses as frost, and the saturation pressure over ice is lower than over supercooled water. The tool uses the ice curve there, as ASHRAE does, so it is strictly a frost point.